Thermal imaging of dampers

July 12, 2011
by Alex Yakimov

From the preliminary investigation we also found that temperature ranges emanating from the floor grilles indicate different temperatures. Prompted by this we’ll set a project task to adjust dampers correctly using anemometer/temperature probe and set a baseline. It will also be included this into regular checks and maintenance procedures.

Image of aisle airflow dampersThermal image of aisle airflow dampers 1Thermal image of aisle airflow dampers 2

 

 

 
 

Thermal imaging of cabinets in the trial area

July 12, 2011
by Alex Yakimov
Image of racks with and without blanking

Image of racks with and without blanking

ABS Consulting have conducted preliminary thermal imaging of some cabinets in the trial area and there is a very visible difference between a cabinet that has no equipment installed and has no blanking and a cabinet that has equipment installed with the gaps blanked off. The images highlight the mixing of warm back into proposed cold through the open cabinet. Temperature diffference can reach 8oC.

Thermal image of racks with and without blanking

Thermal image of racks with and without blanking